Electrical calculations practice for the Texas exams

Ten new problems every set: Ohm's law, single-phase and three-phase power, transformer full-load current, voltage drop, series and parallel resistance, and continuous loads at 125%. Work each one on paper, then open the answer and steps. Built for the Calculations portion of the Texas journeyman and master electrician exams.

Set 20261134

New set

10 problems, all seven types in every set. Work each one before you open its steps.

Problem 1: Series and parallel resistance

Resistors of 8 Ω, 20 Ω and 10 Ω are connected in series. What is the total resistance, in ohms?

Show the answer and steps

Answer: 38 Ω

  1. In series, resistances add: R = R1 + R2 + R3.
  2. R = 8 + 20 + 10 = 38 Ω.

Problem 2: Transformer full-load current

A 25 kVA single-phase transformer has a 480 V winding. What is the full-load current of that winding, in amperes?

Show the answer and steps

Answer: 52.08 A

  1. Single-phase: I = kVA × 1,000 ÷ E.
  2. I = 25 × 1,000 ÷ 480 = 25,000 ÷ 480 = 52.08 A.
  3. The other winding has the same kVA, so its current changes in inverse proportion to its voltage.

Problem 3: Three-phase power

A balanced three-phase load uses 30 kW on 208 V line-to-line at a power factor of 0.95. What is the line current, in amperes?

Show the answer and steps

Answer: 87.65 A

  1. Rearrange P = 1.732 × E × I × PF for current: I = P ÷ (1.732 × E × PF).
  2. Convert kW to watts: 30 × 1,000 = 30,000 W.
  3. 1.732 × 208 × 0.95 = 342.24.
  4. I = 30,000 ÷ 342.24 = 87.66 A.
  5. With the exact square root of 3 the key prints as 87.65 A. Both are inside the self-check tolerance.

Problem 4: Single-phase power

A single-phase load on 208 V draws 24 A at a power factor of 0.85. What is its true power, in watts?

Show the answer and steps

Answer: 4,243 W

  1. Single-phase true power: P = E × I × PF.
  2. Apparent power first: 208 × 24 = 4,992 VA.
  3. True power: 4,992 × 0.85 = 4,243 W.
  4. Sanity check: true power can never be more than the volt-amperes.

Problem 5: Ohm's law

A 208 V source feeds a resistive load of 10 Ω. What current does the load draw, in amperes?

Show the answer and steps

Answer: 20.8 A

  1. Ohm's law solved for current: I = E ÷ R.
  2. I = 208 ÷ 10 = 20.8 A.
  3. Check it back: 20.8 × 10 = 208 V.

Problem 6: Voltage drop

A 240 V single-phase, two-wire circuit carries 80 A to a load 75 ft away (one way). The copper conductors are 1/0 AWG, 105,535 circular mils. Use K = 12.9 Ω·cmil/ft. What is the voltage drop as a percentage of the source voltage?

Show the answer and steps

Answer: 0.61%

  1. Single-phase: VD = 2 × K × I × L ÷ cmil, with L the one-way length.
  2. VD = 2 × 12.9 × 80 × 75 ÷ 105,535 = 1.47 V.
  3. Percent drop = 1.47 ÷ 240 × 100 = 0.61%.

Problem 7: Continuous load at 125%

A branch circuit serves 12 A of continuous load and 4 A of noncontinuous load. What minimum ampere rating does the 125% rule give, before rounding up to a standard size?

Show the answer and steps

Answer: 19 A

  1. Continuous part at 125%: 12 × 1.25 = 15 A.
  2. Add the noncontinuous part at 100%: 15 + 4 = 19 A.
  3. In 2023 NEC numbering the rule is at 210.19(A)(1) for the conductor and 210.20(A) for the overcurrent device; confirm the numbers in your 2026 book. Rounding up to a standard device rating is a separate step this drill leaves out.

Problem 8: Three-phase power

A balanced three-phase load on 240 V line-to-line draws 15 A per line at a power factor of 0.9. What is its true power, in watts?

Show the answer and steps

Answer: 5,612 W

  1. Three-phase true power: P = 1.732 × E × I × PF, with line voltage and line current.
  2. Apparent power: 1.732 × 240 × 15 = 6,235 VA.
  3. True power: 6,235 × 0.9 = 5,612 W.
  4. The common miss is using 3 in place of 1.732, or leaving out the power factor.

Problem 9: Single-phase power

A single-phase load on 208 V draws 30 A at a power factor of 0.85. What is its true power, in watts?

Show the answer and steps

Answer: 5,304 W

  1. Single-phase true power: P = E × I × PF.
  2. Apparent power first: 208 × 30 = 6,240 VA.
  3. True power: 6,240 × 0.85 = 5,304 W.
  4. Sanity check: true power can never be more than the volt-amperes.

Problem 10: Series and parallel resistance

Resistors of 5 Ω, 3 Ω and 40 Ω are connected in series. What is the total resistance, in ohms?

Show the answer and steps

Answer: 48 Ω

  1. In series, resistances add: R = R1 + R2 + R3.
  2. R = 5 + 3 + 40 = 48 Ω.

Score yourself

Give yourself one point for each answer within 0.5% of the key. That leaves room for 1.732 against the exact square root of 3 and for rounding once at the end. Rework every miss by hand from its steps before you start the next set.

Fix a weak type

Studying for TX Journeyman? Take the free 10-question check to see exactly which topics to fix first, then close the gaps with the Bonding Jumper course.

Or read a full free lesson first (no signup).

Studying with a coworker? Send them the free check.

Studying for TX Master? Take the free 10-question check to see exactly which topics to fix first.

Or read a full free lesson first (no signup).

Studying with a coworker? Send them the free check.

How the practice set works

Each set has 10 problems. The first seven cover every type once in a shuffled order, and the last three repeat types at random. Every problem gives you all its numbers, so you need a calculator and nothing else. Open Show the answer and steps only after you have an answer written down.

The set number at the top picks the numbers. The same set number always gives the same ten problems, so quote it with the problem number if you report an error. New set moves to the next set number.

The formulas behind each type

  • Ohm's law. E = I × R, with P = I² × R and P = E² ÷ R when resistance is known.
  • Single-phase power. P = E × I × PF. E × I alone is apparent power in volt-amperes.
  • Three-phase power. P = 1.732 × E × I × PF, with line-to-line voltage and line current.
  • Transformer full-load current. I = kVA × 1,000 ÷ E for single-phase, and kVA × 1,000 ÷ (1.732 × E) for three-phase.
  • Voltage drop. VD = 2 × K × I × L ÷ cmil for single-phase and 1.732 × K × I × L ÷ cmil for three-phase, with L the one-way length. K and the circular mils are given in each problem.
  • Series and parallel resistance. Series resistances add. In parallel, the reciprocal of the total is the sum of the reciprocals.
  • Continuous load at 125%. 1.25 × the continuous load plus the noncontinuous load gives the minimum before you round up to a standard rating. The rule is at 210.19(A)(1) and 210.20(A) in 2023 numbering, so confirm the numbers in your 2026 book.

The first six are standard physics in our own words. The method for the table-driven calculations, by NEC article and table number, is in the Calculations portion guide, and the master Calculations guide works the longer version.

Worked example: a three-phase line current

A balanced 30 kW load runs on 480 V, three-phase, at a power factor of 0.9. Step 1: convert to watts, 30 × 1,000 = 30,000 W. Step 2: the divisor, 1.732 × 480 × 0.9 = 748.22. Step 3: I = 30,000 ÷ 748.22 = 40.09 A. Leaving out the power factor gives 36.09 A, and using 3 in place of 1.732 gives 23.15 A. Both are the kind of wrong option a careful setup avoids. This is an original example, not an exam question.

Calculations practice FAQ

Where do these practice problems come from?

Every problem is original and written to the published PSI outline for the Texas electrician exams, which lists Calculations and Theory, Transformers and Branch Circuit Calculations in the Calculations portion. The numbers are made up and drawn from a seed, and every key comes from the same math as the calculators on this site.

Why are there no ampacity, motor or conduit fill problems?

Those answers come from NEC tables, and we never reproduce code-book values. Every problem here gives you all its inputs, including K and circular mils for voltage drop. Work the table problems from your own NEC with the method in our Calculations portion guide.

Does this help with the Texas master electrician exam too?

Yes. The PSI outline lists Calculations and Theory, Transformers and Branch Circuit Calculations in the master Calculations portion as well, and these formulas are the same at both levels. The master portion adds more service and motor work, which needs your NEC tables.

What calculator can I bring to the exam?

PSI allows only non-programmable calculators that are silent, battery-operated, have no paper tape printing and have no alphabet keyboard. Practice these sets on the calculator you will carry, so the key order is familiar.

Generate ten problems from public physics formulas with seeded numbers, every input given in the question, and show the answer and steps for each. Every key comes from the same math as the calculators on this site. A study aid; the question in front of you and your NEC govern real work.

Try one free question

Check where you stand on TX Journeyman

Scored by domain, untimed. No signup.

Start the free 10-question check

Email me the free TX Journeyman exam-day kit

What to bring, arriving and the testing room, from the exam body's own candidate guide. Sent to your inbox.

Ask Lug before you buy AI your AI study assistant

See what's on the TX Journeyman exam, test yourself with 5 quick questions, or find the plan that fits you.

Sources

The formulas are standard physics and need no code book. The bulletin describes the exam these skills are for.

Practice the Texas journeyman Calculations portion

You just worked the formula half of the Calculations portion. The free 10-question check scores you by topic in minutes, no signup, so you see whether the math or the NEC lookups cost you more. The course drills your weak spots and explains every answer.

Take the free 10-question check

The TX Journeyman course

Available now · instant access

The TX Journeyman course

  • 10modules of lessonsEvery task on the outline
  • 3timed practice exams80 scored questions, 240 minutes; exam day adds 5 unscored
  • 442practice questionsEach one explained
  • 1week-by-week study planSet to your exam date

Turn a practice answer into a study step. In untimed practice, ask Lug AI about any question you answer, follow up, then see your weakest topics and what to drill next.

Texas Journeyman course$99

Terms and refunds · Secure checkout by Stripe · Billed by Nori Software

See the course

Compare plans

Every answer comes with a full explanation.

By the Bonding Jumper editorial team. Report an error with the set number and problem number.

Add this practice set to your site

Copy the HTML with its attribution link. The iframe scrolls through the set and the formulas; no external script is needed. The host must allow this page to be framed.