Electrical Feeders

A 208Y/120-volt, 3-phase feeder supplies 64 A of continuous load and 52 A of noncontinuous load per phase. Terminations are rated 75°C and no ampacity adjustment or correction applies. What is the minimum size of the copper THWN ungrounded conductors?