Try a full lesson: Power supply and loading

This is a complete lesson from the course (module 11 of 12, NICET task 2.3.4), followed by 10 practice questions with full explanations. Nothing to sign up for.

Why this task matters at Level II

At Level I you install what the drawings show. At Level II you are expected to check that the design actually works: that the batteries will carry the system through an outage, that each notification circuit is not overloaded, and that the last strobe on the circuit still gets enough voltage to flash. NICET puts this under task 2.3.4, inside the submittal and layout domain, which is 20 to 30 percent of the Level II exam.

You will not be asked to recite code text. You will be asked to run the numbers and pick the right result, often with the calculator built into the test software. This lesson walks through the three calculations you need, each with a worked example you can repeat with your own figures.

Keep your own copy of NFPA 72 open while you work. We cite sections by number so you can find them; we never reproduce the code's wording.

1. Secondary power: sizing the standby battery

When normal power fails, the batteries have to run the system in standby for a set time and then still power a full alarm. For a typical fire alarm system that means 24 hours of standby followed by 5 minutes of alarm. An emergency voice/alarm communications system needs 15 minutes of alarm at full load instead of 5. Find these in NFPA 72-2022 Chapter 10, under the secondary power supply requirements (section 10.6.7).

The method is the same every time:

  1. Add up the standby current: the panel's own standby draw plus every device that draws current while the system is quiet (detectors, modules, annunciators).
  2. Add up the alarm current: the panel's alarm draw plus everything that turns on in alarm, which is mostly your notification appliances.
  3. Multiply each by its time in hours. Standby is 24 h. Five minutes of alarm is 5/60 = 0.0833 h; fifteen minutes is 0.25 h.
  4. Add the two amp-hour figures.
  5. Add the capacity margin. The margin comes from the code edition your AHJ enforces (Chapter 10) and the panel manufacturer's worksheet, so take it from those. This lesson uses 20 percent as an example input, not as the code figure.
  6. Pick the next standard battery size up, never down.

Worked example

A small office building has a conventional panel and one NAC power supply. From the data sheets:

  • Panel standby 0.120 A, panel alarm 0.250 A
  • 28 smoke detectors at 0.00009 A each in standby (0.0025 A in total)
  • Notification appliances draw nothing in standby and 1.80 A in alarm

Standby current: 0.120 + 0.0025 = 0.1225 A

Alarm current: 0.250 + 1.80 = 2.05 A

Standby amp-hours: 0.1225 A × 24 h = 2.94 Ah

Alarm amp-hours: 2.05 A × 0.0833 h = 0.171 Ah

Total: 2.94 + 0.171 = 3.11 Ah

With a 20 percent margin: 3.11 × 1.2 = 3.73 Ah

The next common size up is a pair of 12 V, 4.5 Ah batteries (wired in series for 24 V). Some designers would choose 7 Ah for future additions, which is fine; choosing 3.5 Ah is not.

What the exam tests here. The common wrong answers come from forgetting to convert 5 minutes to hours (using 5 instead of 0.0833 inflates the alarm term about 60 times), adding the margin to only one of the two terms, or rounding down to a battery that is "close enough".

2. Notification circuit loading

Each notification appliance circuit (NAC) has a current rating, and so does the power supply that feeds it. Before you add appliances, you need to know the circuit can carry them.

  1. Take each appliance's current at the setting you will use. Strobe current changes with the candela setting, so a 75 cd strobe draws more than a 15 cd one. Use the manufacturer's figure for the voltage the circuit will run at; many data sheets list a higher current at the low end of the voltage range, and that is the one to use.
  2. Add them up for the circuit.
  3. Compare the total with the NAC's rating and with whatever is left on the power supply after its other circuits.

Worked example

A NAC is rated 2.5 A. The plan puts these appliances on it (example values, not from a real data sheet):

  • 8 horn-strobes at 15 cd, 0.070 A each = 0.560 A
  • 4 horn-strobes at 75 cd, 0.165 A each = 0.660 A
  • 2 strobes at 110 cd, 0.210 A each = 0.420 A

Circuit total: 0.560 + 0.660 + 0.420 = 1.64 A

That is within the 2.5 A rating with 0.86 A to spare, about 34 percent headroom. If the power supply has two other NACs drawing 1.9 A and 2.1 A and is rated 6.0 A in total, the supply carries 1.64 + 1.9 + 2.1 = 5.64 A, which is within its rating but leaves only 0.36 A. Note that on the submittal: one more circuit of strobes will need another power supply.

3. Voltage drop on a notification circuit

Appliances are listed to work down to a minimum voltage, often 16 V for 24 V regulated appliances. The circuit starts at the lowest voltage the power supply delivers at the end of its battery life (the panel manual gives this; 20.4 V is common for 24 V systems), and the wire eats into that voltage on the way out and back.

  1. Find the wire's resistance per 1,000 ft. For solid uncoated copper, NFPA 70 Chapter 9 Table 8 gives about 3.07 ohms per 1,000 ft for 14 AWG and about 1.93 ohms per 1,000 ft for 12 AWG.
  2. Use the loop length: current goes out and comes back, so double the one-way distance.
  3. Resistance of the run = (ohms per 1,000 ft) × (loop length ÷ 1,000).
  4. Voltage drop = current × resistance (Ohm's law).
  5. Voltage at the last appliance = starting voltage minus drop. It has to be at or above the appliance's listed minimum.

Treating the whole load as if it sat at the far end of the circuit (a "lumped" load) overstates the drop, so if the circuit passes that way it passes. Real designs often split the load into segments for a more accurate figure.

Worked example: does the circuit pass?

Take the 1.64 A circuit above, wired in 14 AWG solid copper, with the last appliance 260 ft from the power supply.

Loop length: 2 × 260 = 520 ft

Resistance: 3.07 × (520 ÷ 1,000) = 1.596 ohms

Voltage drop: 1.64 A × 1.596 ohms = 2.62 V

Voltage at the last appliance: 20.4 - 2.62 = 17.78 V

17.78 V is above the 16 V minimum, so the circuit passes, with 1.78 V to spare.

Worked example: how far can the circuit run?

Turn the question around. With the same 1.64 A load, how long can the 14 AWG circuit be?

Allowed drop: 20.4 - 16.0 = 4.4 V

Maximum resistance: 4.4 V ÷ 1.64 A = 2.68 ohms

Maximum loop length: 2.68 ÷ 3.07 × 1,000 = 873 ft

Maximum one-way length: 873 ÷ 2 = about 437 ft

Moving up to 12 AWG: 2.68 ÷ 1.93 × 1,000 = 1,390 ft of loop, about 695 ft one way. That is the usual fix when a long corridor fails the check, along with splitting the circuit or adding a NAC power supply closer to the load.

What the exam tests here. The classic mistakes are using the one-way length instead of the loop, starting from 24 V instead of the end-of-battery voltage, and using the 15 cd current for a strobe set to a higher candela.

Check yourself

The free practice set below has questions on these three calculations, written in the style of the exam, with a full explanation for every answer.

Where to look in your own books

  • NFPA 72-2022 Chapter 10: power supplies, secondary power capacity (10.6.7) and battery requirements
  • NFPA 72-2022 Chapter 18: notification appliances, including how appliances are listed and installed
  • NFPA 70 (2020) Chapter 9, Table 8: conductor properties
  • The panel and power supply installation manuals: end-of-battery voltage, NAC ratings and battery calculation worksheets

Practice set

Print these questions for a class (PDF) Answer key on page 2. Free, no signup.

Pick an answer, then check it. Every wrong option is explained too.

1. Submittal Preparation and System Layout

A system draws 0.30 A in standby and 3.2 A in alarm. It needs 24 hours of standby followed by 5 minutes of alarm, and the design adds a 20% margin to the total calculated capacity. What is the minimum battery capacity?

2. Submittal Preparation and System Layout

A notification circuit carries 1.2 A, treated as a lumped load at the far end. It is wired in 12 AWG solid copper (1.93 ohms per 1,000 ft) and the last appliance is 400 ft from the power supply. The supply's end-of-battery output is 20.4 V. What voltage reaches the last appliance?

3. Submittal Preparation and System Layout

A NAC rated 2.0 A already carries 1.45 A. You want to add strobes that draw 0.095 A each at the chosen setting. How many can you add without exceeding the circuit rating?

4. Installation

Power-limited fire alarm cable will be run exposed, not in raceway, through a ceiling space used for environmental air (a plenum). Which cable type is suitable?

Hint: where to look

Where to look: NFPA 70 Article 760. Read that part before you pick an answer.

5. Installation

A wall-mounted strobe is being installed in a corridor with a 10 ft ceiling. Where should its height be checked?

Hint: where to look

Where to look: NFPA 72-2022 Chapter 18. Read that part before you pick an answer.

6. Installation

During acceptance testing you find several smoke detectors still wearing the dust covers fitted during construction. What should you do?

Hint: where to look

Where to look: NFPA 72-2022 Chapters 14 and 17. Read that part before you pick an answer.

7. Maintenance

Besides an alarm test, what does a periodic test of a duct smoke detector with sampling tubes need to confirm?

Hint: where to look

Where to look: NFPA 72-2022 Chapter 14. Read that part before you pick an answer.

8. Maintenance

A ground fault trouble appears on one circuit only after heavy rain and clears a day later. Where is the most likely cause?

Hint: where to look

Where to look: NFPA 72-2022 Chapters 12 and 14. Read that part before you pick an answer.

9. Maintenance

After an annual inspection and test, how long must the records be kept?

Hint: where to look

Where to look: NFPA 72-2022 Chapter 14. Read that part before you pick an answer.

10. Management and Supervision

The AHJ acceptance test is booked for Friday, but the elevator contractor cannot attend, so the recall functions cannot be confirmed at the elevators. What is the best action?

Hint: where to look

Where to look: NFPA 72-2022 Chapters 14 and 21. Read that part before you pick an answer.

0 of 10 checkedCheck each answer to see your score.

Practice this module in the course: Power supply and loading

Studying with a coworker? Send them this free lesson.

Free NICET FA II study plan

A week-by-week plan from today to your exam, weighted to the published exam outline. We show it here and email you a copy.

The NICET FA II course

Available now · instant access

Ready for the rest? The full course

  • 12modules of lessonsEvery task on the outline
  • 2full-length timed exams110 questions in 155 minutes each
  • 471practice questionsEach one explained
  • 8worked calculationsStep by step
  • 30code-navigation drillsFind it fast in NFPA 72
  • 1week-by-week study planSet to your exam date

Turn a practice answer into a study step. In untimed practice, ask Strobe AI about any question you answer, follow up, then see your weakest topics and what to drill next.

See all 12 modules
  1. Planning work from field conditions
  2. Circuits, pathways and raceways
  3. Installing equipment
  4. Commissioning
  5. Periodic testing
  6. Impairments and deficiencies
  7. Maintenance documentation
  8. Assembling shop drawing information
  9. Surveying the site
  10. Preparing basic drawings
  11. Power supply and loading
  12. Coordinating the work
Level II course$149Get the Level II course · $149

Instant access. Terms and refunds · Secure checkout by Stripe · Billed by Nori Software

Compare plans

Look inside the course

The screens you get after checkout, with sample answers.

  • Timed exam with flags
    Timed practice exam screen for NICET Fire Alarm Level II with a countdown clock, a flag-for-review button, a sample question, and a numbered question navigator that marks answered and flagged questions.
    Timed exam with flagsThe real-length clock, a flag button on every question and a navigator that shows what you answered and flagged.
  • Review every miss
    Question review screen for NICET Fire Alarm Level II after a timed practice exam. A missed question is open with your choice and the correct answer marked, the explanation below them and the NFPA 72-2022 chapter reference at the bottom.
    Review every missAfter the exam, open any question you missed to see your choice, the correct answer, why, and the NFPA 72 chapter to read.
  • Readiness by domain
    Readiness by domain panel for NICET Fire Alarm Level II. Each domain shows its exam weight, answers given and accuracy, with a drill link under it and the weakest domain called out.
    Readiness by domainEach domain rated from your own answers, with a one-click drill where you need work.

Every answer comes with a full explanation.

Questions are original and written to NICET's published content outline. Code is cited by section number so you can look it up in your own copy. Think something is wrong? Report it.