Try a full lesson: Voltage drop: the calculation and the code status

This is a complete lesson from the course (module 2 of 12, Topic NJ.2), followed by 10 practice questions with full explanations. Nothing to sign up for.

What this lesson covers

Voltage drop is one of the most common calculations on state journeyman exams, and one of the easiest to get wrong by a single factor of 2. Theory and calculations are the largest area on our 100-question practice exam, about 14 questions. This lesson gives you one formula in two forms, a habit for checking it, and the code status of the 3% and 5% figures.

We cite the 2023 NEC by article in our own words. Keep your own copy open beside this page.

Step 1: pick the formula

Use the circular mil method:

  • Single-phase: VD = 2 × K × I × L ÷ CM
  • Three-phase: VD = 1.732 × K × I × L ÷ CM

Where:

  • K is about 12.9 for copper and 21.2 for aluminum (ohm-circular mils per foot, a trade approximation).
  • I is the load current in amperes.
  • L is the one-way length in feet, from source to load.
  • CM is the conductor's area in circular mils, from the conductor properties table in Chapter 9.

The 2 in the single-phase formula is there because current goes out on one conductor and back on the other. The 1.732 in the three-phase formula replaces it, because the return current is shared among the phases.

Step 2: check it with the resistance method

Chapter 9 also lists each conductor's resistance in ohms per 1,000 ft. Then:

  • R = ohms per 1,000 ft × total conductor length ÷ 1,000 (for single-phase, the total length is out and back, 2 × L)
  • VD = I × R

The two methods agree within a few tenths of a volt. Working both is the habit that catches a missing 2.

Step 3: compare it with the target

Divide the drop by the source voltage for a percentage. The NEC's informational notes in Articles 210 and 215 suggest no more than 3% on a branch circuit or feeder and 5% total from the service to the farthest outlet. These are recommendations, not general requirements. A few articles do set mandatory limits for specific equipment; if a question names that equipment, read its article.

Worked examples

Example 1: single-phase drop. A 120 V circuit feeds a 16 A load 75 ft away on 12 AWG copper. Take 12 AWG as 6,530 cmil and 1.98 Ω per 1,000 ft.

The working (2 steps)
  • CM method: 2 × 12.9 × 16 × 75 ÷ 6,530 = 30,960 ÷ 6,530 = 4.74 V, or 4.74 ÷ 120 = 3.95%.
  • Resistance check: 150 ft × 1.98 ÷ 1,000 = 0.297 Ω, and 16 × 0.297 = 4.75 V. Agrees.

Example 2: sizing up to meet 3%. Same circuit. 3% of 120 V is 3.6 V. Solve the formula for CM: CM = 2 × K × I × L ÷ VD = 30,960 ÷ 3.6 = 8,600 cmil. Take 10 AWG as 10,380 cmil: it is the smallest that meets 8,600.

  • Check: 30,960 ÷ 10,380 = 2.98 V, or 2.49%. Under 3%.

Example 3: three-phase. A 480 V, three-phase load draws 65 A at 250 ft on 6 AWG copper. Take 6 AWG as 26,240 cmil and 0.491 Ω per 1,000 ft.

  • CM method: 1.732 × 12.9 × 65 × 250 ÷ 26,240 = 363,071 ÷ 26,240 = 13.84 V, or 13.84 ÷ 480 = 2.88%.
  • Resistance check: one conductor is 250 × 0.491 ÷ 1,000 = 0.1228 Ω, and 65 × 0.1228 = 7.98 V per conductor. Times 1.732 for three-phase line to line: 13.82 V. Agrees.

Example 4: the longest run that meets 3%. A 240 V, single-phase, 40 A load on 8 AWG copper (16,510 cmil). 3% is 7.2 V. Solve for L: L = VD × CM ÷ (2 × K × I) = 7.2 × 16,510 ÷ (2 × 12.9 × 40) = 118,872 ÷ 1,032 = 115 ft.

  • Check: at 115 ft, 2 × 12.9 × 40 × 115 ÷ 16,510 = 7.19 V. Just under 7.2.

Example 5: aluminum. Repeat Example 1 with aluminum of the same area: use K = 21.2. 2 × 21.2 × 16 × 75 ÷ 6,530 = 50,880 ÷ 6,530 = 7.79 V. Check by ratio: 4.74 × (21.2 ÷ 12.9) = 7.79 V. Aluminum drops about 64% more than copper of the same size.

What a drop does to the load

A resistive load's power changes with the square of its voltage. A 240 V, 4,800 W heater has R = 240² ÷ 4,800 = 12 Ω. At 228 V (a 5% drop), P = 228² ÷ 12 = 4,332 W. Check by ratio: 0.95² × 4,800 = 4,332 W. Motors respond differently: lower voltage makes them draw more current and run hotter.

Common traps

  • Doubling the length and keeping the 2. L is one way. The formula's 2 covers the return.
  • Using 2 on three-phase. Use 1.732. Using 2 overstates the drop by about 15%.
  • Using the wrong voltage for the percentage. Divide by the circuit's source voltage: 120 V for a 120 V circuit, 480 V for a 480 V three-phase circuit.
  • Calling 3% a requirement. It is an informational note unless a specific article requires a limit.
  • Rounding the conductor down. If the CM you need falls between sizes, take the larger.
  • Forgetting the EGC. If you upsize the phase conductors for voltage drop, the equipment grounding conductor grows in proportion (Article 250; see Module 6).

Check yourself

Try the ten questions in the free practice set for this lesson. Work each one twice, once each way.

Where to look in the NEC

  • Chapter 9: conductor properties (circular mils and resistance per 1,000 ft)
  • Articles 210 and 215: voltage drop informational notes
  • Article 250: proportional increase of the equipment grounding conductor

Practice set

Print these questions for a class (PDF) Answer key on page 2. Free, no signup.

Pick an answer, then check it. Every wrong option is explained too.

1. Electrical Theory and Calculations

Why does the single-phase voltage drop formula multiply by 2?

2. Electrical Theory and Calculations

A 240 V, single-phase load draws 24 A at 120 ft on 10 AWG copper. Take 10 AWG as 10,380 circular mils and K as 12.9. What is the voltage drop?

3. Electrical Theory and Calculations

A 120 V circuit at the end of a long run has a voltage drop of 12 V. What percentage drop is that?

4. Electrical Theory and Calculations

A 120 V, single-phase, 20 A load is 90 ft away. Using K = 12.9, which is the smallest copper conductor that keeps the drop at 3% or less? Take 12 AWG as 6,530 cmil, 10 AWG as 10,380, 8 AWG as 16,510 and 6 AWG as 26,240.

5. Electrical Theory and Calculations

A 208 V, three-phase load draws 50 A at 150 ft on 6 AWG copper. Take 6 AWG as 26,240 circular mils and K as 12.9. What is the voltage drop?

6. Electrical Theory and Calculations

A single-phase circuit carries 16 A to a load 180 ft away on 10 AWG copper. Take its resistance as 1.24 Ω per 1,000 ft. Using the resistance method, what is the voltage drop?

7. Electrical Theory and Calculations

A circuit's load current and conductor size stay the same, but the run is twice as long. What happens to the voltage drop?

8. Electrical Theory and Calculations

For ordinary branch circuits and feeders, what is the code status of the 3% and 5% voltage drop figures in the 2023 NEC?

9. Electrical Theory and Calculations

A 120 V, single-phase, 12 A load is supplied on 12 AWG copper (6,530 circular mils). Using K = 12.9, what is the longest one-way run that keeps the drop at 3% or less?

10. Electrical Theory and Calculations

A 240 V, 4,800 W resistive heater has only 228 V at its terminals because of voltage drop. About how much power does it produce?

0 of 10 checkedCheck each answer to see your score.

Practice this module in the course: Electrical theory and calculations

Studying with a coworker? Send them this free lesson.

Free Journeyman study plan

A week-by-week plan from today to your exam, weighted to the published exam outline. We show it here and email you a copy.

The Journeyman course

Available now · instant access

Ready for the rest? The full course

  • 12modules of lessonsEvery task on the outline
  • 2timed practice exams100 questions in 240 minutes, full length at our estimate
  • 298practice questionsEach one explained
  • 1week-by-week study planSet to your exam date

Turn a practice answer into a study step. In untimed practice, ask Lug AI about any question you answer, follow up, then see your weakest topics and what to drill next.

See all 12 modules
  1. Definitions, general requirements and plan reading
  2. Electrical theory and calculations
  3. Branch circuits
  4. Services, feeders and load calculations
  5. Overcurrent protection
  6. Grounding and bonding
  7. Conductors and cables
  8. Raceways, boxes and fill
  9. Lighting, signs and utilization equipment
  10. Motors, controls and transformers
  11. Special occupancies and special equipment
  12. Low-voltage systems, fire alarm and job safety
Journeyman course$99Get the Journeyman course · $99

Instant access. Terms and refunds · Secure checkout by Stripe · Billed by Nori Software

    Compare plans

    Every answer comes with a full explanation.

    Questions are original and written to TDLR's published content outline. Code is cited by section number so you can look it up in your own copy. Think something is wrong? Report it.